Online Voltage Regulation System (AVC)
RUHSTRAT OLIVER AVC voltage optimization equipment operates like an online system, providing a new type of unstable power protection. This system can correct voltage deviations in real time (response time 140μs, correction time <5ms, usually within 2ms) and is easier to integrate into industrial facilities than uninterruptible power supply equipment. Compared to uninterruptible power supply equipment, the grid short-circuit capacity basically remains unchanged, and existing protective devices such as fuses and circuit breakers can continue to operate.
- Commodity name: Online Voltage Regulation System (AVC)
- Commodity ID: Online Voltage Regulation System
Category:
- Product Description
- Summary
-
Working Principle
The online voltage regulation system consists of a rectifier, inverter, bypass protection thyristor switch, and injection transformer. Whether during normal operation or voltage sags, the system remains online in real time. When a voltage sag occurs on the system side, the rectifier and inverter inside the device generate a corresponding compensation voltage, which is injected into the original power supply system through the injection transformer, thereby achieving online voltage sag regulation. When an internal fault occurs in the online voltage regulation system, the bypass protection thyristor switch quickly (at the microsecond level) disconnects the regulation system from the power supply system.
Technical Parameters
Serial Number
Project Category
Parameter
Input Characteristics
Grid Voltage Range
AC400V±15%
Rated Power
50/60Hz±10%
Overvoltage Level
III
40% Correction Range
30 Correction Range
Output
Correction Time
Output Characteristics
Three-phase Voltage Sag Correction
60%
70%
100%
30s
50%
60%
90%
20s
30%
35%
55%
5s
Single-phase Voltage Sag Correction
40%
55%
100%
30s
0%
5%
55%
5s
Voltage Swell Correction
130%
130%
100%
30s
120%
120%
100%
60s
Continuous Regulation
90%
90%
100%
Continuous
110%
110%
100%
Continuous
Response Time
Response time 140μs, regulation time <10ms (usually 2ms)
Accuracy
<1%
Capacity
150kVA/300 kVA /450 kVA /600 kVA /750 kVA /900 kVA /1200 kVA /1500 kVA /1800 kVA
Output Wiring Method
Three-phase Four-wire System
Cooling Method
Air Cooling
Output Frequency
50/60Hz±1%
Overload Capacity
150%——30s
Voltage Distortion (THDu)
Under linear load conditions, THDu < 2.5%
Voltage Unbalance (Negative Sequence/Positive Sequence)
Under 100% unbalanced load conditions < 3%
Protection Current
200%
Noise
<65dB
Protection Functions
Power-on self-test, power semiconductor device fault protection, DC bus overvoltage, DC bus undervoltage, fan protection, voltage and current transformer disconnection protection, overload protection
Display
5.7-inch Touch Screen
Communication
Modbus/TCP, Ethernet/485
-
RUHSTRAT OLIVER AVC voltage optimization equipment operates like an online system, providing a new type of unstable power protection. This system can correct voltage deviations in real time (response time 140μs, correction time <5ms, usually within 2ms) and is easier to integrate into industrial facilities than uninterruptible power supply equipment. Compared to uninterruptible power supply equipment, the grid short-circuit capacity basically remains unchanged, and existing protective devices such as fuses and circuit breakers can continue to operate.
Keywords:
Get a Quote
Note: Please leave your contact information, our professionals will contact you as soon as possible!