All
  • All
  • Product Management
  • News and Information
  • Introduction Content
  • Company Outlets
  • Frequently Asked Questions
  • Company Video
  • Company Album

Product center

  • SSOC30.jpg
SSOC30.jpg
+

SSOC30 Switchgear Intelligent Measurement and Display Unit

SSOC30 not only features dynamic simulation diagrams, digital display of cabinet temperature and humidity with programmable control, live display and interlocking, intelligent voice error prevention prompts, control transfer switches (including energy storage switch, remote/local transfer switch, circuit breaker transfer switch), RS485 digital communication, and other functions, but it also integrates all functions of a multifunctional electric energy meter. It can simultaneously measure and display various electrical parameters: three-phase voltage, three-phase current, active power, reactive power, power factor, frequency, and measure active and reactive electric energy. Additionally, it can be optionally configured with high-voltage live self-test functions, phase sequence/voltage detection ports, and other functional modules.

  • Commodity name: SSOC30 Switchgear Intelligent Measurement and Display Unit
  • Commodity ID: SSOC30
  • Product Description
  • Summary
  • Application Functions:

    Function

    SSOC30

    Dynamic Simulation Diagram

    Anti-misoperation Voice Prompt

    Live Display and Interlock

    Temperature and Humidity Digital Display and Control

    Remote/Local, Open/Close Switch, Energy Storage, Lighting and Other Operation Switches

    Main Circuit Power Parameter Measurement

    Contact/Cable Online Temperature Measurement

    None

    RS-485 Communication

    √ (Standard with 1 channel, optional upgrade to 2 channels RS485 communication)

    Event Recording Function

    None

    Human Body Sensor Probe

    Optional

    High Voltage Live Self-check

    Optional

    Phase Verification/Voltage Detection Port

    Optional

    Open and Close Status Indication

    Optional

    Open/Close Circuit Voltage Measurement

    Optional

     

    Technical Parameters:

    Technical Parameters

    SSOC33

    Operating Power Supply

    AC/DC85~265V

    Maximum Power Consumption

    9VA

    Temperature Measurement Range

    -40~120℃

    Humidity Measurement Range

    0~99%RH

    Relay Output Capacity

    AC220V/5A

    Communication

    RS485 Interface, Modbus - RTU

    Communication Baud Rate

    4800, 9600bps

    Voltage Input

    Three-phase three-wire: 100V; Three-phase four-wire: 57.7V

    Current Input

    AC1A, 5A

    Accuracy Level

    Reactive power energy is level 1, others are level 0.5

    Operating Environment

    Temperature: -10~+60℃, Relative Humidity: ≤95%, No Corrosive Gas, Altitude ≤2500m

    Isolation Withstand Voltage

    Between Power/Input/Output > 2kV

    Cutout Size

    220×166mm

     

    Function Notes:

    Dynamic Simulation Diagram:

    Based on the user's primary system diagram and voltage level (35KV in yellow, 10KV in dark red, 6KV in blue), a mask is created. The break points (such as circuit breakers, truck positions, grounding switches, energy storage, etc.) are represented by dynamic indication modules, forming real-time dynamic indications to provide operators with more intuitive, richer, and more accurate status information. The indications include:

    ■ Circuit Breaker Open Indication   ■ Circuit Breaker Close Indication   ■ Truck Working Position Indication

    ■ Truck Test Position Indication   ■ Energy Storage Indication     ■ Grounding Indication

    Anti-misoperation Voice Prompt:

    ■ When the circuit breaker is neither in the working position nor the test position, the working and test position indicator lights flash simultaneously. If the circuit breaker is in the closed state at this time (red vertical simulation bar lit), a voice prompt "Please open the circuit breaker" will sound until the operator performs the open operation. This prevents the operator from mistakenly forcing the truck to the working position when the circuit breaker is closed.

    ■ When the circuit breaker is neither in the working position nor the test position (working and test position indicator lights flash simultaneously) or is in the working position (working position indicator light lit), if the grounding switch is mistakenly forced closed causing the grounding closed indicator light to turn on, a voice prompt "Please open the grounding switch" will sound.

    ■ When the above two misoperations occur simultaneously, a voice prompt "Please open the circuit breaker, please open the grounding switch" will sound.

    Live Display and Interlock:

    ■ Live Display LED Starting Voltage (KV): Rated Phase Voltage × (0.15~0.65)

    ■ Forced Interlock Starting Control Voltage (KV): Below Rated Phase Voltage × 0.65

    ■ When any one of the three phases is live, the relay in the interlock control part is disconnected, prohibiting the electromagnetic lock from operating; when all three phases are not live simultaneously, the interlock release light turns on, the relay closes, allowing the electromagnetic lock to operate.

    Note: Forced interlock control power supply: AC or DC 220V, which can protect the reliable operation of the interlock part. If the control power supply disappears during operation, the interlock contacts will not malfunction, and the locked equipment remains reliably locked.

    Temperature and Humidity Digital Display and Control:

    Can support 1 to 2 temperature and humidity sensors and output contacts, displaying the on-site temperature and humidity values. Users can set the upper and lower limits for heating/dehumidification output as needed. When the ambient temperature ≥40℃, heating stops unconditionally to prevent overheating damage.

    Operation Functions/Operation Switches:

    ■ Remote/Local Operation  ■ Open/Close Operation  ■ Energy Storage Operation  ■ Lighting Operation

    Power Parameter Measurement:

    Input the secondary side voltage and current of the transformer; it can measure and display the three-phase voltage, three-phase current, active power, reactive power, power factor, frequency, and other parameters of the primary side power network, and measure active and reactive electrical energy (reactive energy accuracy is level 1, others are level 0.5).

    RS485 Communication:

    Digital communication uses RS485 communication interface and MODBUS communication protocol. Through the RS485 interface, multiple intelligent switchgear operation display devices can be networked for communication.

    Human body induction probe:

    When someone stands in front of the cabinet, the device automatically activates the LCD backlight and provides voice prompts when powered on; it automatically stops after the operator leaves.

    High voltage live self-test function:

    The high voltage live self-test button is a self-reset button (non-locking). When the main unit is powered but the three phases are not powered, pressing the self-test switch will light up the three-phase high voltage indicator lights powered by the internal power supply. The unlocked state switches to the locked state (unlock light off), and the electromagnetic lock output relay is disconnected.

    Voltage detection/phase verification test port:

    The control device provides a set of (3-phase) external voltage detection/phase verification test ports, which need to be used with a voltage detector/phase verifier (purchased separately); if the voltage detector/phase verifier is inserted into a certain phase sequence port and ground port of the voltage detection terminal and shows a display, it indicates the tested phase sequence is live; if the voltage detector/phase verifier is inserted into the same phase sequence port of two control devices and shows no display, it indicates the phase sequences are the same.

  • SSOC30 not only features dynamic simulation diagrams, digital display of cabinet temperature and humidity with programmable control, live display and interlocking, intelligent voice error prevention prompts, control transfer switches (including energy storage switch, remote/local transfer switch, circuit breaker transfer switch), RS485 digital communication, and other functions, but it also integrates all functions of a multifunctional electric energy meter. It can simultaneously measure and display various electrical parameters: three-phase voltage, three-phase current, active power, reactive power, power factor, frequency, and measure active and reactive electric energy. Additionally, it can be optionally configured with high-voltage live self-test functions, phase sequence/voltage detection ports, and other functional modules.

Keywords:

Get a Quote

Note: Please leave your contact information, our professionals will contact you as soon as possible!