Wind Turbine Unit Temperature Rise Arc Flash Protection System

SPR63 series fan unit temperature rise arc flash protection device, mainly used in wind turbines, realizes arc flash monitoring and early warning for wind turbines, as well as cable temperature rise monitoring and early warning. Designed for remote operation and maintenance of wind turbines, providing data support for equipment selection. According to the type of configured arc flash sensor, the device is divided into: SPR63-OP fiber optic temperature rise arc flash protection device, and SPR63-WT photoelectric temperature rise arc flash protection device.

  • Commodity name: Wind Turbine Unit Temperature Rise Arc Flash Protection System
  • Commodity ID: SPR 63-OP/WT
  • Product Description
  • Summary
  • Arc Flash Protection Main Unit

    SPR63-OP Device

    SPR63-OP is a fiber optic temperature rise arc flash protection device, specially designed for remote operation and maintenance of wind turbines. It is suitable for monitoring and alarming arc flash, joint temperature, and current. The device consists of a main unit, photoelectric conversion module, electric temperature sensor, arc flash sensor, optical fiber, and installation accessories. The arc flash sensors are divided into all-optical, white light, and ultraviolet types, with adjustable optical fiber action intensity thresholds. The photoelectric module supports hot swapping.

    Technical Parameters

    ■ Compact size, DIN rail mounting

    ■ 100~240V ac/dc power input

    ■ 2 sets of three-phase current monitoring

    ■ 6 channels of fiber optic arc flash sensor input

    ■ 32 channels of passive wireless electric temperature collection

    ■ 5 large-capacity programmable trip output contacts

    ■ Alarm and trip logic can be set to three modes: "Current", "Arc Flash", "Arc Flash + Current"

    ■ RS485 and RJ45 communication ports, supporting MODBUS communication protocol

    SPR63-WT Device

    SPR63-WT is a photoelectric temperature rise arc flash protection device, mainly composed of an arc flash main unit, arc flash sensor, and electric temperature sensor. It monitors arc flash in generators, inverters, transformer boxes, and high and low voltage side switches of wind turbines. The arc flash sensor only supports ultraviolet light and is insensitive to everyday light sources.

    Technical Parameters

    ■ Compact size, DIN rail mounting

    ■ 100~240V ac/dc power input

    ■ Three-phase current monitoring

    ■ 9 channels of arc flash point sensor input

    ■ 32 channels of passive wireless electric temperature collection

    ■ 6 large-capacity programmable trip output contacts

    ■ Alarm and trip logic can be set to three modes: "Current", "Arc Flash", "Arc Flash + Current"

    ■ Built-in RS485 communication port, supporting MODBUS communication protocol

     

    Arc Flash and Electric Temperature Sensors

    Fiber Optic Sensors

    ■ Sensors are divided into three types: all-optical, white light, and ultraviolet light

    ■ Ultraviolet sensors do not respond to visible light; this avoids false triggers caused by flashlight illumination during power site inspections;

    ■ Wide detection range, detection angle exceeds 240 degrees

    ■ Spectral response bandwidth: 280nm~400nm

    ■ Standard ST fiber optic interface packaging

    ■ Operating temperature -40~+85℃

    Photoelectric Sensors

    ■ Light intensity >8000Lux activation

    ■ 270° detection range

    ■ Meets IP61 vibration requirements

    ■ Insensitive to everyday light sources

  • SPR63 series fan unit temperature rise arc flash protection device, mainly used in wind turbines, realizes arc flash monitoring and early warning for wind turbines, as well as cable temperature rise monitoring and early warning. Designed for remote operation and maintenance of wind turbines, providing data support for equipment selection. According to the type of configured arc flash sensor, the device is divided into: SPR63-OP fiber optic temperature rise arc flash protection device, and SPR63-WT photoelectric temperature rise arc flash protection device.